Precont® PS4SC
At the moment, the product is not available in our warehouse.
After placing the order, we will notify you of the expected delivery date of the product.
Free delivery
from 1000 PLN (net)
Ask an experienced consultant:
Pressure switch for supervision of absolute and relative pressures in gases, vapors, liquids and dust
- Highly accurate and long-term stable ceramic measuring cell
- Many variants of flush process connections
- Bright LED display
Due to the device construction as well as the availability of a variety of hygienic resp. standard process connections the device Precont® PS4SC is especially suitable for the use for hygienic and aseptic applications in food and beverage industry, pharmaceutical industry, biotechnology and sterile process engineering as well as general applications in machinery and plant engineering, air-conditioning and refrigeration plant engineering, hydraulic and pneumatic systems, process industry and environmental technology.
The pressure switch is suitable for demanding measuring requirements.
Due to its high accuracy and the high flexibility of configuration, the device can be suited a wide variety of applications.
The pressure switch with front-flush diaphragm has been specifically designed for the measurement of viscous, paste-like, adhesive, crystallizing, particle-laden and contaminated media, which would clog the pressure channel of conventional process connections.
The front-flush diaphragm is completely welded with the process connection and supplied with a positive seal. A reliable, dead-space free sealing between the process connection and the process adapter resp. measuring medium is thus assured.
The robust design and the high-quality workmanship turns the device into a very high quality product, which even the most adverse environmental conditions cannot affect, whether the lowest temperatures when used outdoors, extreme shock and vibration or aggressive media.
A captive laser marking of the type label ensures the identifiability throughout the entire lifetime of the device. Obviously is the optional marking of a measurement point designation resp. TAG, a customer label or of a neutral type label, of course also per laser marking.
A LABS-free resp. silicone-free version, a factory calibration with calibration certificate and a customer specific configuration resp. preset is also optionally available like a material test certificate EN10204 3.1 or factory certifications for drink water resp. food suitability.
Hilfsenergie | |
Versorgungsspannung | 10,5 V bis 30 V DC, verpolungsgeschützt |
Stromaufnahme | ≤ 60mA Analogausgang max. 22,5mA (Schaltausgänge im Leerlauf) |
Schaltausgang S1 / S2 | |
Funktion | PNP-schaltend auf +L |
Ausgangsstrom | 0 bis ≤ 200mA Strombegrenzt Kurzschlussfest |
Analogausgang – Strom 4…20mA | |
Arbeitsbereich | 3,9mA bis 21mA min. 3,8mA max. 22mA |
Zulässige Bürde | ≤ (US – 10,5V) / 20mA |
Bereitschaftszeit | ≤ 1ms |
Messgenauigkeit | |
Kennlinienabweichung | ≤ ±0,2% FS |
Langzeitdrift | ≤ ±0,1% FS/Jahr, nicht kumulativ |
Temperaturabweichung | Nullpunkt: ≤ ±0,015% FS/K, max. ±0,75% (-20°C bis +80°C) Spanne: ≤ ±0,015% FS/K, max. ±0,5% (-20°C bis +80°C / > 400mbar) Spanne: ≤ ±0,015% FS/K, max. ±0,8% (-20°C bis +80°C / ≤ 400mbar) |
Werkstoffe | |
Membrane (prozessberührend) | Keramik Al2O3 96% Keramik Al2O3 99,7% Keramik Al2O3 99,9% |
Prozessanschluss (prozessberührend) | Stahl 1.4404 (316L) Stahl 1.4571 (316Ti) |
Anschlussgehäuse | CrNi-Stahl |
Dichtungen (prozessberührend) | FPM – Fluorelastomer (Viton®) EPDM – Etylen-Propylen-Dienmonomer, FDA-gelistet FFKM – Perfluorelastomer (z.B. Kalrez®) FFKM hd – Perfluorelastomer hochdicht |
Umgebungsbedingungen | |
Umgebungstemperatur | -40°C bis +85°C |
Prozesstemperatur | -40°C bis +125°C |
Prozessdruckbereiche | -1 bis +60bar (typabhängig) |