Precont-XDS100BVA1710R1S
In order to select a replacement, contact our consultant.
Ask an experienced consultant:
Precont-XDS100BVA1710R1S Pressure Transmiter
Main features
Measurement of absolute or relative pressure
in gases, vapors, liquids and dust.
Finely graded pressure measuring
• Measuring ranges from -1 to 60bar, gauge
• Measuring ranges from 0 to 60bar, absolute
• Measuring spans from 0,1 to 60bar
Ceramic membrane for various applications
Process temperature range from –40°C to +125°C
ATEX II 1/2 G Ex ia IIC T4 Ga/Gb
ATEX II 1/2 D Ex ia IIIC T60°C/T102°C Da/Db
Certification for the use in explosion hazardous areas
High accuracy ≤ 0,05% - Xcellence / ≤ 0,1% / ≤ 0,2%
Integrated evaluation electronic
• 2-wire with current signal 4…20mA
• 3-wire with voltage signal 0...10V
• 2x PNP switch output
LED display for best readability
Precont XDS10 Przetwornik Ciśnienia
Auxiliary power supply
output signal 4…20mA (with display) | 14,5 V…45 V DC |
14,5 V…30 V DC (with Ex variant) | |
output signal 4…20mA (without display) | 10,5 V…45 V DC |
10,5 V…30 V DC (with Ex variant) | |
output signal 0…10V | 14,5 V…45 V DC |
14,5 V…30 V DC (with Ex variant) |
Supply current
2-wire 4…20mA | ≤ 22mA (PNP-switching outputs in neutral) |
3-wire 0…10V | ≤ 10mA (PNP-switching outputs in neutral) |
2xPNP-switching output
Function | PNP-switching on +Vs |
Output current | ≤ 250mA |
current limited | |
short circuit protected |
Measurement accuracy
Characteristics deviation | ≤ ±0,05 / 0,1% / 0,2% FS |
Long term drift | ≤ ± 0,1% FS / year not cumulative |
Temperature deviation | ≤ ± 0,15% FS / 10 K (Zero / Span) (Zero / Span) |
Materials
Membrane (medium contact) | Ceramics AL2O3 99,9% |
Process connection (medium contact) | Steel 1.4404 / 316L resp. 1.4571 / 316 Ti) |
Connection housing | CrNi-steel / PBT polybutylene terephthalate / POM – polyoxymethylene (Delrin®) |
Gaskets (medium contact) | EPDM – ethylene-propylene-diene monomer |
CR – chloroprene rubber (Neopren®) | |
FFKM – perfluorelastomere (Kalrez®) | |
NBR – nitrile-butadiene rubber |
Environmental conditions
Ambient temperature | -40°C…+85°C |
Process temperatures | – 40°C…+100°C resp. +125°C |
Process pressure ranges | – 1 bar …60 bar |
Turn-Down | 30:1 |
Schutzart | IP65 / IP67 (EN/IEC 60529) |