Thermocont® TU4S
In order to select a replacement, contact our consultant.
Ask an experienced consultant:
Universal temperature transmitter / temperature switch for general industrial applications
- Compact design
- integrated 2-wire electronic 4…20mA
- Hart protocol programming
Suitable for general applications in
- Machinery and plant engineering
- Air-conditioning and refrigeration plant engineering
- Hydraulic and pneumatic systems
- Process industry
- Environmental technology
The device is an electronic temperature transmitter / temperature switch for monitoring, control and continuous measurement of temperatures.
A high variety of versions of process connections and electronic types allows the use for a wide range of applications, also for demanding measuring requirements.
Due to its high accuracy and the digital adjustability by HART®, RS485 Modbus®-RTU or IO-Link® the device can be suited to a wide variety of applications.
The optional drift monitoring and redundancy function increases the process safety. At exceedance of the set drift limit a signal will be generated immediately and thus, the product quality will be improved significantly.
Due to the use of two redundantly working sensors, which are mutually monitored, the calibration intervals can be increased und thus calibrations can be saved.
The pressure switch with front-flush O-ring gasket has been specifically designed for the measurement of viscous, paste-like, adhesive, crystallizing, particle-laden and contaminated media.
The robust design and the high-quality workmanship turns the device into a very high quality product, which even the most adverse environmental conditions cannot affect, whether the lowest temperatures when used outdoors, extreme shock and vibration stress or aggressive media.
A captive laser marking of the type label ensures the identifiability throughout the entire lifetime of the device.
Obviously is the optional marking of a measurement point designation resp. TAG, a customer label or of a neutral type label, of course also per laser marking.
A LABS- resp. silicone-free version, a factory calibration with calibration certificate and a customer specific configuration resp. preset is also optionally available like a material test certificate EN10204 3.1 or a factory certifications for drink water suitability.
Customer specific special versions can be realized short-term on request, e.g. special designs for the process connection or other process materials.
Measuring range | |
Nominal temperature | -50°C…+200°C |
Output type A – Current 4…20mA HART® | |
Analogue output | 3,9mA…20,5mA ≥ 3,8mA ≤ 22mA dI ≤ 1µA |
Time behavior | T90 ≤ 8ms ton ≤ 0,2s |
Interface | HART®-compliant (7.0) 1200 Bit/s |
Output type V – RS485 Modbus®-RTU | |
Interface | RS485, bidirectional Modbus®-RTU 9600 Baud (4800…38400 Baud) |
Time behavior | T90 ≤ 2ms ton ≤ 0,1s |
Output type L – IO-Link® | |
Interface | IO-Link® V1.1 Com2 (38400 Baud) |
Analogue output 0…20mA | 0…20,5mA ≤ 0,05mA ≤ 22mA dI ≤ 1µA |
Analogue output 4…20mA | 3,8…20,5mA ≥ 3,6mA ≤ 22mA dI ≤ 1µA |
Switch output | 2x PP (Push-Pull), switch to +L/-L |
Output | Uout ≤ 0,2V, ≥ Us – 2V Iout = 0…200mA (current limited ≤ 450mA, short circuit protected) |
Time behavior | T90 ≤ 2ms ton ≤ 0,1s |
Auxiliary power | |
Supply voltage | Typ A: 9…35 V DC Typ V: 6…35 V DC Typ L: 9…35 V DC (without IO-Link®) Typ L: 18…30 V DC (with IO-Link®) |
Measuring accuracy | |
Characteristic deviation | ≤ ±(0,25K + 0,002 * [t]) |
Long term drift | ≤ ±0,1K/year |
Temperature deviation | ≤ ±0,2K |
Process conditions | |
Process temperature | Standard: -50°C…+100°C Extended: -50°C…+200°C |
Process pressure | ≤ 100 bar |
Environmental conditions | |
Environmental temperature | -40°C…+100°C |
Protection level | IP69K/IP67 (EN/IEC 60529) |
MTTF | 463 years |