« Back
IV0009 - Inductive sensor

IV0009 - Inductive sensor

PRODUCENT CODE: IV0009
CATEGORY: Sensors with long sensing range
Producer: ifm electronic
498.93 PLN
(net)
7-14 days
The product is available on request
At the moment, the product is not available in our warehouse.
After placing the order, we will notify you of the expected delivery date of the product.
Fast shipping
Free delivery
from 1000 PLN (net)
Do you have questions about the product?
Ask an experienced consultant:
+48 32 237 61 98 w. 101
bn@newtech.com.pl
Description
IVE2020-FBKA
  • Five positions of the sensing face selectable
  • Long sensing range for high uptime
  • Robust housing for use in harsh industrial environments
  • For use in materials handling
  • Output function normally open / normally closed programmable
Technical data
Product characteristics
Output function normally open / normally closed; (selectable)
Sensing range [mm] 20
Housing rectangular
Dimensions [mm] 40 x 40 x 118
Electrical data
Operating voltage [V] 24...250 AC / 24...230 DC
Protection class II
Reverse polarity protection yes
Outputs
Output function normally open / normally closed; (selectable)
Max. voltage drop switching output DC [V] 5
Max. voltage drop switching output AC [V] 8
Minimum load current [mA] 5
Max. leakage current [mA] 1.5
Permanent current rating of switching output AC [mA] 500
Permanent current rating of switching output DC [mA] 500
Switching frequency AC [Hz] 30
Switching frequency DC [Hz] 100
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Detection zone
Sensing range [mm] 20
Real sensing range Sr [mm] 20 ± 10 %
Operating distance [mm] 0...16.2
Accuracy / deviations
Correction factor steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminium: 0.4 / copper: 0.3
Hysteresis [% of Sr] 1...10
Switch point drift [% of Sr] -10...10
Operating conditions
Ambient temperature [°C] -25...85
Note on ambient temperature
for UL application: ...70 °C
Max. height above sea level [m] 2000
Protection IP 67
Tests / approvals
EMC
EN 61000-4-2 ESD 8 kV CD / 8 kV AD
EN 61000-4-3 HF radiated 10 V/m
EN 61000-4-4 Burst 2 kV
EN 61000-4-6 HF conducted 15 V
EN 55011 Class A
Vibration resistance
EN 60068-2-6 Fc 10 g (10...2000 Hz) / 50 sweep cycles, 1 octave per minute, in 3 axes
Shock resistance
EN 60068-2-27 Ea 30 g 11 ms half-sine; 3 shocks each in every direction of the 3 coordinate axes
Continuous shock resistance
EN 60068-2-27 40 g 6 ms; 4000 shocks each in every direction of the 3 coordinate axes
Fast temperature change
EN 60068-2-14 Na TA = -40 °C; TB = 85 °C; t1 = 30 min; t2 = < 10 s; 50 cycles
MTTF [years] 272.6
UL approval
Ta 0...70 °C
Enclosure type Type 1
File number UL E174191
Notes For use in NFPA 79 applications only
Mechanical data
Weight [g] 268
Housing rectangular
Mounting flush mountable
Dimensions [mm] 40 x 40 x 118
Materials PA 6.6; diecast zinc epoxy coated; sensing face: PA 6.6; LED window: PA; screws: stainless steel stainless steel (1.4305 / 303)
Displays / operating elements
Display
switching status 1 x LED, yellow
operation 1 x LED, green
Electrical connection
Required protection ≤ 3 A und ≥ 300 V AC/DC
Remarks
Remarks
5 positions of the active zone possible
Cable gland (E11270) to be ordered separately
Pack quantity 1 pcs.
Electrical connection
Connection terminals: ...2.5 mm²; Cable gland: M20 X 1.5