« Back
PI2203 - Flush pressure sensor with display

PI2203 - Flush pressure sensor with display

PRODUCENT CODE: PI2203
CATEGORY: Use in process technology at high temperatures
Producer: ifm electronic
3581.25 PLN
(net)
7-14 days
The product is available on request
At the moment, the product is not available in our warehouse.
After placing the order, we will notify you of the expected delivery date of the product.
Fast shipping
Free delivery
from 1000 PLN (net)
Do you have questions about the product?
Ask an experienced consultant:
+48 32 237 61 98 w. 101
bn@newtech.com.pl
Description
PI-025-REZ01-MFRKG/US/ /P
  • For use in high temperatures in the food and beverage industry
  • Robust stainless steel housing with hygienic front-flush design
  • With two-wire and three-wire connection technology
  • Reduced wiring complexity when operated as two-wire current loop
  • Integrated clamp diaphragm seal with stainless steel membrane
Technical data
Product characteristics
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Measuring range
-1...25 bar-14.4...362.7 psi-0.1...2.5 MPa
Process connection Clamp DN40 (1,5") DIN 32676 (ISO 2852)
Application
Special feature Gold-plated contacts
Application flush mountable for the food and beverage industry
Media viscous media and liquids with suspended particles; liquids and gases
Medium temperature -20...200; (-20...90 < 0 bar)
Min. bursting pressure
150 bar2175 psi15 MPa
Pressure rating
80 bar1160 psi8 MPa
Type of pressure relative pressure; vacuum
Electrical data
Min. insulation resistance 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Integrated watchdog yes
2-wire
Operating voltage 20...32 DC
Current consumption 3.6...21
Power-on delay time 1
3-wire
Operating voltage 18...32 DC
Current consumption < 45
Power-on delay time 0.5
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs 2
Output signal switching signal; analogue signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / normally closed; (parameterisable)
Number of analogue outputs 1
Analogue current output 4...20, invertible; (scalable)
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
2-wire
Max. load 300
3-wire
Max. voltage drop switching output DC 2
Permanent current rating of switching output DC 250
Switching frequency DC 125
Max. load (Ub - 10 V) / 20 mA
Measuring/setting range
Measuring range
-1...25 bar-14.4...362.7 psi-0.1...2.5 MPa
Set point SP
-0.96...25 bar-13.8...362.7 psi-0.096...2.5 MPa
Reset point rP
-1...24.96 bar-14.4...362.1 psi-0.1...2.496 MPa
Analogue start point
-1...18.74 bar-14.4...271.8 psi-0.1...1.874 MPa
Analogue end point
5.24...25 bar76.2...362.7 psi0.524...2.5 MPa
In steps of
0.02 bar0.3 psi0.002 MPa
Factory setting
SP1 = 6.24 barrP1 = 5.74 bar
SP2 = 18.74 barrP2 = 18.24 bar
ASP = 0.00 barAEP = 25.00 bar
Accuracy / deviations
Switch point accuracy < ± 0,2; (Turn down 1:1)
Repeatability < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation < ± 0,2; (Turn down 1:1 , linearity, incl. hysteresis and repeatability , limit value setting to DIN EN IEC 62828-1)
Linearity deviation < ± 0,15; (Turn down 1:1)
Hysteresis deviation < ± 0,15; (Turn down 1:1)
Long-term stability < ± 0,1; (Turn down 1:1; per year)
Temperature coefficient zero point < ± 0,2; (0...200 °C)
Temperature coefficient span < ± 0,15; (0...200 °C)
Response times
Damping process value dAP 0...30
Damping for the analogue output dAA 0.01...99.99
2-wire
Step response time analogue output 45
3-wire
Min. response time of switching output (dAP) 3
Step response time analogue output 7
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.0
SDCI standard IO-Link Communication Specification, Version 1.0, January 2009, Ordner No: 10.002
Profiles no profile
SIO mode yes
Required master port type A
Process data analogue 1
Process data binary 2
Min. process cycle time 2.3
Supported DeviceIDs
Type of operationDeviceID
default102
Operating conditions
Ambient temperature -25...80
Note on ambient temperature
Medium temperature: ≤ 160 °C
Ambient temperature -25...65
Note on ambient temperature
Medium temperature: ≤ 200 °C
Storage temperature -25...100
Protection IP 67; IP 68; IP 69K
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-2750 g (11 ms)
Vibration resistance
DIN EN 60068-2-620 g (10...2000 Hz)
MTTF 142
Note on approval
Including free 6-point calibration certificate.
Mechanical data
Weight 1066.3
Housing cylindrical
Dimensions Ø 50 / L = 163
Materials stainless steel (316L/1.4404); stainless steel (316L/1.4435); PBT; PEI; PFA
Materials (wetted parts) stainless steel (316L/1.4435)
Min. pressure cycles 10 million
Process connection Clamp DN40 (1,5") DIN 32676 (ISO 2852)
Surface characteristics Ra/Rz of the wetted parts < 0.38 / -
Fill fluid for pressure transmission NEOBEE (food grade, FDA compliant)
Diaphragm diameter 34
Displays / operating elements
Display
Display unitLED, green
switching statusLED, yellow
function displayalphanumeric display, 4-digit
measured valuesalphanumeric display, 4-digit
Display unit bar; psi; MPa; % of the span
Remarks
Pack quantity 1 pcs.
Electrical connection