Number of inputs and outputs |
Number of digital outputs: 1; Number of analogue outputs: 1 |
Measuring range |
-1...6 bar | -14.5...87 psi | -100...600 kPa |
|
Process connection |
threaded connection G 1/2 external thread |
Special feature |
Gold-plated contacts |
Measuring element |
ceramic-capacitive pressure measuring cell |
Temperature monitoring |
yes |
Application |
flush mountable for industrial applications; for industrial applications |
Media |
viscous media and liquids with suspended particles; Liquids; other media on request |
Medium temperature [°C] |
-25...110; (flush mount zero-leak using metal-to-metal seal. for permissible temperatures of other sealing versions, see sealing materials under "Accessories") |
Min. bursting pressure |
120 bar | 1740 psi | 12000 kPa |
|
Pressure rating |
|
Vacuum resistance [mbar] |
-1000 |
Type of pressure |
relative pressure; vacuum |
No dead space |
yes |
Operating voltage [V] |
9.6...30 DC |
Min. insulation resistance [MΩ] |
100; (500 V DC) |
Protection class |
III |
Reverse polarity protection |
yes |
Integrated watchdog |
yes |
Current consumption [mA] |
3.5...21.5 |
Power-on delay time [s] |
< 1 |
Current consumption [mA] |
< 30 |
Power-on delay time [s] |
< 0.5 |
Number of inputs and outputs |
Number of digital outputs: 1; Number of analogue outputs: 1 |
Total number of outputs |
2 |
Output signal |
analogue signal; IO-Link (configurable) |
Number of digital outputs |
1; (IO-Link) |
Number of analogue outputs |
1 |
Analogue current output [mA] |
4...20; (scalable; 1:5) |
Max. load [Ω] |
(Ub - 9,6 V) / 21,5 mA; 670 Ω (Ub = 24 V) |
Short-circuit proof |
yes |
Overload protection |
yes |
Measuring range |
-1...6 bar | -14.5...87 psi | -100...600 kPa |
|
Analogue start point |
-1...4.8 bar | -14.5...69.6 psi | -100...480 kPa |
|
Analogue end point |
1...6 bar | 14.5...87 psi | 20...600 kPa |
|
In steps of |
0.002 bar | 0.1 psi | 0.2 kPa |
|
Factory setting |
ASP = 0.0 bar | AEP = 6.0 bar | | ASP = 0.0 kPa | AEP = 600kPa | | ASP = 0.0 psi | APE = 87 psi | |
|
Measuring range |
-25...110 °C | -13...230 °F |
|
Repeatability [% of the span] |
< ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
Characteristics deviation [% of the span] |
< ± 0,5; (linearity incl. hysteresis and repeatability, limit value setting to DIN EN IEC 62828-1) |
Linearity deviation [% of the span] |
< ± 0,15; (Turn down 1:1) |
Hysteresis deviation [% of the span] |
< ± 0,15; (Turn down 1:1) |
Long-term stability [% of the span] |
< ± 0,1; (Turn down 1:1; per year) |
Temperature coefficient zero point [% of the span / 10 K] |
< ± 0,1 (-25...85 °C) < ± 0,3 (85...110 °C) |
Temperature coefficient span [% of the span / 10 K] |
< ± 0,1 (-25...85 °C) < ± 0,3 (85...110 °C) |
Accuracy [K] |
± 2.5 K + (0.045 x (ambient temperature - medium temperature)) |
Damping process value dAP [s] |
0...99.99 |
Damping for the analogue output dAA [s] |
0...99.99 |
Step response time analogue output [ms] |
12 |
Step response time analogue output [ms] |
3 |
Dynamic response T05 / T09 [s] |
< 10 / < 25; (DIN EN 60751 water; &rt; 0,9 m/s) |
Communication interface |
IO-Link |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.1 |
SDCI standard |
IEC 61131-9 |
Profiles |
Smart Sensor ED2: Identification and Diagnosis (0x4000), Measurement Data Channel (0x800A) |
SIO mode |
no |
Required master port type |
A; (when pin 2 not connected: B) |
Min. process cycle time [ms] |
3.5 |
IO-Link resolution pressure [kPa] |
0.002 |
IO-Link resolution temperature [K] |
0.2 |
IO-Link process data (cyclical) |
function | bit length |
---|
pressure | 16 | temperature | 16 | device status | 4 |
|
IO-Link functions (acyclical) |
application specific tag; internal temperature |
Supported DeviceIDs |
Type of operation | DeviceID |
---|
default | 1434 |
|
Ambient temperature [°C] |
-25...90 |
Storage temperature [°C] |
-40...100 |
Protection |
IP 67; IP 68; IP 69 |
EMC |
|
Shock resistance |
DIN EN 60068-2-27 | 50 g (11 ms) |
|
Vibration resistance |
DIN EN 60068-2-6 | 20 g (10...2000 Hz) |
|
MTTF [years] |
427 |
UL approval |
Enclosure type | Type 1 | UL Approval no. | J050 | File number UL | E174189 |
|
Weight [g] |
85.4 |
Materials |
stainless steel (1.4435 / 316L); stainless steel (1.4404 / 316L); PA; PTFE; FKM |
Materials (wetted parts) |
stainless steel (1.4435 / 316L); Al2O3 (ceramics); surface characteristics : Ra < 0,4 / Rz 4; PTFE; (FKM for sealing with seal DIN EN ISO 1179-2, see operating instructions) |
Min. pressure cycles |
100 million |
Tightening torque [Nm] |
25 |
Process connection |
threaded connection G 1/2 external thread |
Display |
operating status | 2 LED, green |
|
Items supplied |
Gasket: G1/2, FKM DIN EN ISO1179-2 (-15...110°C), E30492 |
|
Accessories (optional) |
Gasket: G1/2, FKM DIN EN ISO1179-2 (-15...110°C), E30492 | Gasket: G1/2, EPDM DIN EN ISO1179-2 (-25...110°C), E30451 | Gasket: G1/2, FFKM DIN EN ISO1179-2 (-5...110°C), E30513 | O-ring: 16,4 x 1, FKM (-15...110°C), E30510 | O-ring: 16,4 x 1, EPDM (-25...110°C), E30511 | O-ring: 16,4 x 1, FFKM (-5...110°C), E30512 |
|
Pack quantity |
1 pcs. |
Connection |
Connector: 1 x M12; coding: A; Contacts: gold-plated |