« Back
PM1115 - Flush pressure sensor

PM1115 - Flush pressure sensor

PRODUCENT CODE: PM1115
CATEGORY: Flush transmitters for the process technology
Producer: ifm electronic
7-14 days
The product is available on request
At the moment, the product is not available in our warehouse.
After placing the order, we will notify you of the expected delivery date of the product.
Fast shipping
Free delivery
from 1000 PLN (net)
Do you have questions about the product?
Ask an experienced consultant:
+48 32 237 61 98 w. 101
bn@newtech.com.pl
Description
PM-006-REZ01-E-ZVG/US
  • Robust stainless steel housing for use in the food and beverage industry
  • Hygienic, flush design
  • Resistant to high-pressure cleaning with aggressive cleaning agents
  • High temperature resistance and high protection rating
IO-Link features
  • Precise analogue output and user-friendly communication via IO-Link
Technical data
Product characteristics
Number of inputs and outputs Number of digital outputs: 1; Number of analogue outputs: 1
Measuring range
-1...6 bar -14.5...87 psi -100...600 kPa
Process connection Clamp DN25...DN40 (1...1,5") DIN 32676 (ISO 2852)
Application
Special feature Gold-plated contacts
Measuring element ceramic-capacitive pressure measuring cell
Temperature monitoring no
Application flush mountable for the food and beverage industry
Media viscous media and liquids with suspended particles; liquids and gases
Medium temperature [°C] -25...150
Min. bursting pressure
100 bar 1450 psi 10000 kPa
Pressure rating
30 bar 435 psi 3000 kPa
Note on pressure rating
take into account the pressure resistance of the bracket and the seal used for clamp connection
Vacuum resistance [mbar] -1000
Type of pressure relative pressure; vacuum
No dead space yes
MAWP (for applications according to CRN) [bar] 30
Electrical data
Operating voltage [V] 18...30 DC
Min. insulation resistance [MΩ] 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Integrated watchdog yes
Current consumption [mA] 3.5...21.5
Power-on delay time [s] 1
Current consumption [mA] < 45
Power-on delay time [s] 0.5
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 1; Number of analogue outputs: 1
Outputs
Total number of outputs 2
Output signal analogue signal; IO-Link; (configurable)
Number of digital outputs 1; (IO-Link)
Number of analogue outputs 1
Analogue current output [mA] 4...20; (scalable)
Max. load [Ω] 700; (Ub = 24 V; (Ub - 9 V) / 21.5 mA)
Short-circuit proof yes
Overload protection yes
Measuring/setting range
Measuring range
-1...6 bar -14.5...87 psi -100...600 kPa
Analogue start point
-1...4.8 bar -14.5...69.6 psi -100...480 kPa
Analogue end point
0.2...6 bar 2.9...87 psi 20...600 kPa
In steps of
0.02 bar 0.05 psi 0.2 kPa
Factory setting
ASP = 0.0 bar AEP = 6.0 bar
Accuracy / deviations
Repeatability [% of the span] < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation [% of the span] < ± 0,2; (linearity incl. hysteresis and repeatability, limit value setting to DIN EN IEC 62828-1)
Linearity deviation [% of the span] < ± 0,15; (Turn down 1:1)
Hysteresis deviation [% of the span] < ± 0,15; (Turn down 1:1)
Long-term stability [% of the span] < ± 0,1; (Turn down 1:1; per year)
Temperature coefficient zero point [% of the span / 10 K] < ± 0,05
Temperature coefficient span [% of the span / 10 K] < ± 0,15
Notes on the accuracy / deviation for further details see section Diagrams and graphs
Response times
Damping for the analogue output dAA [s] 0...4
Step response time analogue output [ms] 30
Step response time analogue output [ms] 7
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
Profiles Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000)
SIO mode no
Required master port type A
Process data analogue 3
Min. process cycle time [ms] 3.2
IO-Link resolution pressure [bar] 0.002
IO-Link process data (cyclical)
function bit length
pressure 16
device status 4
IO-Link functions (acyclical) application specific tag; internal temperature
Supported DeviceIDs
Type of operation DeviceID
default 663
Operating conditions
Ambient temperature [°C] -25...80
Storage temperature [°C] -40...100
Protection IP 67; IP 68; IP 69K
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-27 50 g (11 ms)
Vibration resistance
DIN EN 60068-2-6 20 g (10...2000 Hz)
MTTF [years] 323
Note on approval
factory certificate available as download at www.factory-certificate.ifm
UL approval
UL Approval no. J055
File number UL E174189
Mechanical data
Weight [g] 393.6
Materials stainless steel (1.4404 / 316L); PBT
Materials (wetted parts) ceramics (99.9 % Al2O3); stainless steel (1.4435 / 316L); surface characteristics: Ra < 0,4 / Rz 4; PTFE
Min. pressure cycles 100 million
Process connection Clamp DN25...DN40 (1...1,5") DIN 32676 (ISO 2852)
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; coding: A; Contacts: gold-plated
ambient temperature influence on the accuracy
X temperature
Y total deviation