PN014A - Pressure sensor with display
PRODUCENT CODE: PN014A
CATEGORY: Use in hazardous areas
Producer: ifm electronic
2076.88 PLN
(net)
7-14 days
The product is available on request
At the moment, the product is not available in our warehouse.
After placing the order, we will notify you of the expected delivery date of the product.
At the moment, the product is not available in our warehouse.
After placing the order, we will notify you of the expected delivery date of the product.
Fast shipping
Free delivery
from 1000 PLN (net)
Free delivery
from 1000 PLN (net)
Do you have questions about the product?
Ask an experienced consultant:
Ask an experienced consultant:
Description
PN-010-RBR14-QFPKG/US/3D /V
- For applications in hazardous areas
- Two switching outputs, one of which can be configured as diagnostic output
- Clearly visible 4-digit LED display
- Robust stainless steel housing for use in harsh industrial environments
- Lifespan of more than 100 million pressure cycles
IO-Link features
- Convenient operation via buttons or parameter setting via IO-Link
Technical data
Product characteristics | |||||||||||
Number of inputs and outputs | Number of digital outputs: 2 | ||||||||||
Measuring range |
|
||||||||||
Process connection | threaded connection G 1/4 internal thread | ||||||||||
Application | |||||||||||
Special feature | Gold-plated contacts | ||||||||||
Application | for industrial applications | ||||||||||
Media | liquids and gases | ||||||||||
Medium temperature [°C] | -20...60 | ||||||||||
Min. bursting pressure |
|
||||||||||
Pressure rating |
|
||||||||||
Type of pressure | relative pressure; vacuum | ||||||||||
Electrical data | |||||||||||
Operating voltage [V] | 18...36 DC; (to SELV/PELV) | ||||||||||
Current consumption [mA] | < 50 | ||||||||||
Protection class | III | ||||||||||
Reverse polarity protection | yes | ||||||||||
Overvoltage protection | yes; (< 40 V) | ||||||||||
Power-on delay time [s] | 0.3 | ||||||||||
Integrated watchdog | yes | ||||||||||
Inputs / outputs | |||||||||||
Number of inputs and outputs | Number of digital outputs: 2 | ||||||||||
Outputs | |||||||||||
Total number of outputs | 2 | ||||||||||
Output signal | switching signal; IO-Link; (configurable) | ||||||||||
Electrical design | PNP/NPN | ||||||||||
Number of digital outputs | 2 | ||||||||||
Output function | normally open / normally closed; (parameterisable) | ||||||||||
Max. voltage drop switching output DC [V] | 2 | ||||||||||
Permanent current rating of switching output DC [mA] | 250 | ||||||||||
Switching frequency DC [Hz] | < 170 | ||||||||||
Short-circuit protection | yes | ||||||||||
Type of short-circuit protection | pulsed | ||||||||||
Measuring/setting range | |||||||||||
Measuring range |
|
||||||||||
Set point SP |
|
||||||||||
Reset point rP |
|
||||||||||
In steps of |
|
||||||||||
Factory setting |
|
||||||||||
Accuracy / deviations | |||||||||||
Switch point accuracy [% of the span] | < ± 0,5 | ||||||||||
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) | ||||||||||
Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) | ||||||||||
Hysteresis deviation [% of the span] | < ± 0,25 | ||||||||||
Long-term stability [% of the span] | < ± 0,05; (per 6 months) | ||||||||||
Temperature coefficient zero point [% of the span / 10 K] | 0,2; (0...60 °C) | ||||||||||
Temperature coefficient span [% of the span / 10 K] | 0,2; (0...60 °C) | ||||||||||
Response times | |||||||||||
Delay time programmable dS, dr [s] | 0; 0,2...50 | ||||||||||
Software / programming | |||||||||||
Parameter setting options | hysteresis / window; normally open / normally closed; diagnostic function; switching logic; switch-on/switch-off delay; Damping; Display unit | ||||||||||
Interfaces | |||||||||||
Communication interface | IO-Link | ||||||||||
Transmission type | COM2 (38,4 kBaud) | ||||||||||
IO-Link revision | 1.1 | ||||||||||
SDCI standard | IEC 61131-9 CDV | ||||||||||
Profiles | no profile | ||||||||||
SIO mode | yes | ||||||||||
Required master port type | A | ||||||||||
Process data analogue | 1 | ||||||||||
Process data binary | 2 | ||||||||||
Min. process cycle time [ms] | 2.3 | ||||||||||
Supported DeviceIDs |
|
||||||||||
Operating conditions | |||||||||||
Ambient temperature [°C] | -20...60 | ||||||||||
Storage temperature [°C] | -40...100 | ||||||||||
Protection | IP 65 | ||||||||||
Tests / approvals | |||||||||||
ATEX marking | II 3D Ex tc IIIC T80°C Dc X | ||||||||||
EMC |
|
||||||||||
Shock resistance |
|
||||||||||
Vibration resistance |
|
||||||||||
MTTF [years] | 194 | ||||||||||
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request | ||||||||||
Mechanical data | |||||||||||
Weight [g] | 304 | ||||||||||
Materials | stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PEI; FKM; EPDM/X; PTFE | ||||||||||
Materials (wetted parts) | stainless steel (1.4305 / 303); ceramics; FKM | ||||||||||
Min. pressure cycles | 100 million | ||||||||||
Process connection | threaded connection G 1/4 internal thread | ||||||||||
Restrictor element integrated | no (can be retrofitted) | ||||||||||
Displays / operating elements | |||||||||||
Display |
|
||||||||||
Remarks | |||||||||||
Pack quantity | 1 pcs. | ||||||||||
Electrical connection |