Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Measuring range |
-1...25 bar | -14.5...362.5 psi | -0.1...2.5 MPa |
|
Process connection |
threaded connection G 1/4 external thread (DIN EN ISO 1179-2); internal thread:M5 |
Special feature |
Gold-plated contacts |
Measuring element |
ceramic-capacitive pressure measuring cell |
Application |
for industrial applications |
Media |
liquids and gases |
Medium temperature [°C] |
-25...80 |
Min. bursting pressure |
|
Pressure rating |
|
Vacuum resistance [mbar] |
-1000 |
Type of pressure |
relative pressure; vacuum |
Operating voltage [V] |
18...30 DC; (to SELV/PELV) |
Current consumption [mA] |
< 35 |
Min. insulation resistance [MΩ] |
100; (500 V DC) |
Protection class |
III |
Reverse polarity protection |
yes |
Power-on delay time [s] |
0.3 |
Integrated watchdog |
yes |
Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Total number of outputs |
2 |
Output signal |
switching signal; analogue signal; IO-Link; (configurable) |
Electrical design |
PNP/NPN |
Number of digital outputs |
2 |
Output function |
normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] |
2 |
Permanent current rating of switching output DC [mA] |
250 |
Switching frequency DC [Hz] |
< 500 |
Number of analogue outputs |
1 |
Analogue current output [mA] |
4...20; (scalable 1:5) |
Max. load [Ω] |
500 |
Analogue voltage output [V] |
0...10; (scalable 1:5) |
Min. load resistance [Ω] |
2000 |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Overload protection |
yes |
Measuring range |
-1...25 bar | -14.5...362.5 psi | -0.1...2.5 MPa |
|
Analogue start point |
-1...20 bar | -14.5...290 psi | -0.1...2 MPa |
|
Analogue end point |
4...25 bar | 58...362.5 psi | 0.4...2.5 MPa |
|
Set point SP |
-0.85...25 bar | -12...362.5 psi | -0.085...2.5 MPa |
|
Reset point rP |
-0.95...24.9 bar | -13.5...361 psi | -0.095...2.49 MPa |
|
Min. difference between SP and rP |
0.15 bar | 1.5 psi | 0.015 MPa |
|
In steps of |
0.05 bar | 0.5 psi | 0.005 MPa |
|
Set point SP |
-0.84...25 bar | -12.2...362.6 psi | -0.084...2.5 MPa |
|
Reset point rP |
-0.95...24.9 bar | -13.7...361.1 psi | -0.095...2.49 MPa |
|
Min. difference between SP and rP |
0.11 bar | 1.5 psi | 0.011 MPa |
|
In steps of |
0.01 bar | 0.1 psi | 0.001 MPa |
|
Switch point accuracy [% of the span] |
< ± 0,4; (Turn down 1:1) |
Repeatability [% of the span] |
< ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
Characteristics deviation [% of the span] |
< ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting) |
Hysteresis deviation [% of the span] |
< ± 0,1; (Turn down 1:1) |
Long-term stability [% of the span] |
< ± 0,05; (Turn down 1:1; per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] |
< ± 0,2; (-0...80 °C) |
Temperature coefficient span [% of the span / 10 K] |
< ± 0,2; (-0...80 °C) |
Notes on the accuracy / deviation |
switch point accuracy, linearity error under DNV GL: < ± 1%: < ± 1% |
Response time [ms] |
< 1.5 |
Delay time programmable dS, dr [s] |
0...50 |
Damping process value dAP [s] |
0...4 |
Damping for the analogue output dAA [s] |
0...4 |
Max. response time analogue output [ms] |
3 |
Parameter setting options |
hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output |
Communication interface |
IO-Link |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.1 |
SDCI standard |
IEC 61131-9 |
SIO mode |
yes |
Required master port type |
A; (when pin 2 not connected: B) |
Supported DeviceIDs |
Type of operation | DeviceID |
---|
Factory setting / CMPT = 2 | 462 | Status_B High Resolution / CMPT = 3 | 973 |
|
Note |
For further information please see the IODD PDF file under "Downloads" |
|
Profiles |
Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
Min. process cycle time [ms] |
2.3 |
IO-Link resolution pressure [bar] |
0.01 |
IO-Link process data (cyclical) |
function | bit length |
---|
pressure | 14 | binary switching information | 2 |
|
IO-Link functions (acyclical) |
application specific tag |
Profiles |
Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000) |
Min. process cycle time [ms] |
3 |
IO-Link resolution pressure [bar] |
0.01 |
IO-Link process data (cyclical) |
function | bit length |
---|
pressure | 16 | device status | 4 | binary switching information | 2 |
|
IO-Link functions (acyclical) |
application specific tag |
Ambient temperature [°C] |
-25...80 |
Storage temperature [°C] |
-40...100 |
Protection |
IP 65; IP 67 |
EMC |
DIN EN 61000-6-2 | | DIN EN 61000-6-3 | |
|
Shock resistance |
DIN EN 60068-2-27 | 50 g (11 ms) |
|
Vibration resistance |
DIN EN 60068-2-6 | 20 g (10...2000 Hz) |
|
MTTF [years] |
138 |
UL approval |
|
Pressure Equipment Directive |
Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Weight [g] |
263.5 |
Materials |
stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC |
Materials (wetted parts) |
stainless steel (1.4404 / 316L); Al2O3 (ceramics); FKM |
Min. pressure cycles |
100 million |
Tightening torque [Nm] |
25...35; (recommended tightening torque; depends on lubrication, seal and pressure rating) |
Process connection |
threaded connection G 1/4 external thread (DIN EN ISO 1179-2); internal thread:M5 |
Process connection sealing |
FKM (DIN EN ISO 1179-2) |
Restrictor element integrated |
no (can be retrofitted) |
Display |
Display unit | 3 x LED, green (bar, psi, MPa) | switching status | 2 x LED, yellow | measured values | alphanumeric display, red/green 4-digit |
|
Pack quantity |
1 pcs. |
Connection |
Connector: 1 x M12; coding: A; Contacts: gold-plated |