PP001E - Pressure switch with ceramic measuring cell
PRODUCENT CODE: PP001E
CATEGORY: Two switching outputs
Producer: ifm electronic
1099.57 PLN
(net)
7-14 days
The product is available on request
At the moment, the product is not available in our warehouse.
After placing the order, we will notify you of the expected delivery date of the product.
At the moment, the product is not available in our warehouse.
After placing the order, we will notify you of the expected delivery date of the product.
Fast shipping
Free delivery
from 1000 PLN (net)
Free delivery
from 1000 PLN (net)
Do you have questions about the product?
Ask an experienced consultant:
Ask an experienced consultant:
Description
PP-250-SBG14-QFPKG/US/ /V
- Suited for use in mobile machines
- Two switching outputs, one of which can be configured as diagnostic output
- High shock and vibration resistance
- Excellent EMC resistance
IO-Link features
- User-friendly communication and parameterisation via IO-Link
Technical data
Product characteristics | |||||||||||||||||||
Number of inputs and outputs | Number of digital outputs: 2 | ||||||||||||||||||
Measuring range |
|
||||||||||||||||||
Process connection | threaded connection G 1/4 external thread internal thread:M5 | ||||||||||||||||||
Application | |||||||||||||||||||
Application | for mobile applications | ||||||||||||||||||
Media | liquids and gases | ||||||||||||||||||
Conditionally suitable for | use in gases at pressures &rt; 25 bar only on request | ||||||||||||||||||
Medium temperature [°C] | -25...90 | ||||||||||||||||||
Min. bursting pressure |
|
||||||||||||||||||
Pressure rating |
|
||||||||||||||||||
Type of pressure | relative pressure | ||||||||||||||||||
Electrical data | |||||||||||||||||||
Operating voltage [V] | 9.6...36 DC; (communication mode: 18...32) | ||||||||||||||||||
Current consumption [mA] | < 45 | ||||||||||||||||||
Min. insulation resistance [MΩ] | 100; (500 V DC) | ||||||||||||||||||
Protection class | III | ||||||||||||||||||
Reverse polarity protection | yes | ||||||||||||||||||
Power-on delay time [s] | 0.3 | ||||||||||||||||||
Inputs / outputs | |||||||||||||||||||
Number of inputs and outputs | Number of digital outputs: 2 | ||||||||||||||||||
Outputs | |||||||||||||||||||
Total number of outputs | 2 | ||||||||||||||||||
Output signal | switching signal; IO-Link; (configurable) | ||||||||||||||||||
Electrical design | PNP | ||||||||||||||||||
Number of digital outputs | 2 | ||||||||||||||||||
Output function | normally open / normally closed; (parameterisable) | ||||||||||||||||||
Max. voltage drop switching output DC [V] | 2 | ||||||||||||||||||
Permanent current rating of switching output DC [mA] | 250 | ||||||||||||||||||
Switching frequency DC [Hz] | 170 | ||||||||||||||||||
Short-circuit protection | yes | ||||||||||||||||||
Type of short-circuit protection | pulsed | ||||||||||||||||||
Overload protection | yes | ||||||||||||||||||
Measuring/setting range | |||||||||||||||||||
Measuring range |
|
||||||||||||||||||
Set point SP |
|
||||||||||||||||||
Reset point rP |
|
||||||||||||||||||
In steps of |
|
||||||||||||||||||
Factory setting |
|
||||||||||||||||||
Accuracy / deviations | |||||||||||||||||||
Switch point accuracy [% of the span] | < ± 0,5 | ||||||||||||||||||
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) | ||||||||||||||||||
Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) | ||||||||||||||||||
Hysteresis deviation [% of the span] | < ± 0,1 | ||||||||||||||||||
Long-term stability [% of the span] | < ± 0,1; (per year) | ||||||||||||||||||
Temperature coefficient zero point [% of the span / 10 K] | < ± 0,2; (0...80 °C) | ||||||||||||||||||
Temperature coefficient span [% of the span / 10 K] | < ± 0,2; (0...80 °C) | ||||||||||||||||||
Response times | |||||||||||||||||||
Response time [ms] | < 3 | ||||||||||||||||||
Damping process value dAP in steps [s] | 0,003 - 0,006 - 0,010 - 0,017 - 0,060 - 0,125 - 0,250 - 0,500 | ||||||||||||||||||
Interfaces | |||||||||||||||||||
Communication interface | IO-Link | ||||||||||||||||||
Transmission type | COM2 (38,4 kBaud) | ||||||||||||||||||
IO-Link revision | 1.0 | ||||||||||||||||||
Profiles | no profile | ||||||||||||||||||
SIO mode | yes | ||||||||||||||||||
Required master port type | A | ||||||||||||||||||
Process data analogue | 1 | ||||||||||||||||||
Process data binary | 2 | ||||||||||||||||||
Min. process cycle time [ms] | 2.3 | ||||||||||||||||||
Supported DeviceIDs |
|
||||||||||||||||||
Operating conditions | |||||||||||||||||||
Ambient temperature [°C] | -25...85 | ||||||||||||||||||
Storage temperature [°C] | -40...100 | ||||||||||||||||||
Protection | IP 68; (7 days / 1 m water depth / 0.1 bar) | ||||||||||||||||||
Tests / approvals | |||||||||||||||||||
EMC |
|
||||||||||||||||||
Shock resistance |
|
||||||||||||||||||
Vibration resistance |
|
||||||||||||||||||
MTTF [years] | 310 | ||||||||||||||||||
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request | ||||||||||||||||||
Mechanical data | |||||||||||||||||||
Weight [g] | 218 | ||||||||||||||||||
Materials | stainless steel (1.4301 / 304); FKM; EPDM/X; PA | ||||||||||||||||||
Materials (wetted parts) | stainless steel (1.4305 / 303); ceramics; FKM | ||||||||||||||||||
Min. pressure cycles | 100 million | ||||||||||||||||||
Process connection | threaded connection G 1/4 external thread internal thread:M5 | ||||||||||||||||||
Restrictor element integrated | yes | ||||||||||||||||||
Displays / operating elements | |||||||||||||||||||
Display |
|
||||||||||||||||||
Teach function | yes | ||||||||||||||||||
Remarks | |||||||||||||||||||
Pack quantity | 1 pcs. | ||||||||||||||||||
Electrical connection | |||||||||||||||||||
Connection | Connector: 1 x M12; coding: A |