PV7604 - Pressure switch with IO-Link
PRODUCENT CODE: PV7604
CATEGORY: Two switching outputs
Producer: ifm electronic
649.47 PLN
(net)
7-14 days
The product is available on request
At the moment, the product is not available in our warehouse.
After placing the order, we will notify you of the expected delivery date of the product.
At the moment, the product is not available in our warehouse.
After placing the order, we will notify you of the expected delivery date of the product.
Fast shipping
Free delivery
from 1000 PLN (net)
Free delivery
from 1000 PLN (net)
Do you have questions about the product?
Ask an experienced consultant:
Ask an experienced consultant:
Description
PV-010-SEN14-UFRVG/US/ /
- Compact housing for use where space is restricted
- Very high overpressure and vacuum resistance
- Robust stainless steel housing with high shock and vibration resistance
- Lifespan of more than 60 million pressure cycles
- Two programmable switching outputs, one of them with IO-Link communication interface
IO-Link features
- User-friendly communication and parameterisation via IO-Link
Technical data
Product characteristics | |||||||||||||
Number of inputs and outputs | Number of digital outputs: 2 | ||||||||||||
Measuring range |
|
||||||||||||
Process connection | threaded connection 1/4" NPT external thread internal thread:M5 | ||||||||||||
Application | |||||||||||||
Measuring element | metallic thin film cell | ||||||||||||
Application | for industrial applications | ||||||||||||
Media | liquids and gases | ||||||||||||
Medium temperature [°C] | -40...90 | ||||||||||||
Min. bursting pressure |
|
||||||||||||
Pressure rating |
|
||||||||||||
Note on pressure rating |
|
||||||||||||
Vacuum resistance [mbar] | -1000 | ||||||||||||
Type of pressure | relative pressure | ||||||||||||
MAWP (for applications according to CRN) [bar] | 25 | ||||||||||||
Electrical data | |||||||||||||
Operating voltage [V] | 18...30 DC | ||||||||||||
Current consumption [mA] | < 15 | ||||||||||||
Min. insulation resistance [MΩ] | 100; (500 V DC) | ||||||||||||
Protection class | III | ||||||||||||
Reverse polarity protection | yes | ||||||||||||
Power-on delay time [s] | < 0.3 | ||||||||||||
Inputs / outputs | |||||||||||||
Number of inputs and outputs | Number of digital outputs: 2 | ||||||||||||
Outputs | |||||||||||||
Total number of outputs | 2 | ||||||||||||
Output signal | switching signal; IO-Link; (configurable) | ||||||||||||
Electrical design | PNP/NPN | ||||||||||||
Number of digital outputs | 2 | ||||||||||||
Output function | normally open / normally closed; (parameterisable) | ||||||||||||
Max. voltage drop switching output DC [V] | 2 | ||||||||||||
Permanent current rating of switching output DC [mA] | 100 | ||||||||||||
Switching frequency DC [Hz] | < 170 | ||||||||||||
Short-circuit protection | yes | ||||||||||||
Type of short-circuit protection | pulsed | ||||||||||||
Overload protection | yes | ||||||||||||
Measuring/setting range | |||||||||||||
Measuring range |
|
||||||||||||
Set point SP |
|
||||||||||||
Reset point rP |
|
||||||||||||
In steps of |
|
||||||||||||
Factory setting |
|
||||||||||||
Accuracy / deviations | |||||||||||||
Switch point accuracy [% of the span] | < ± 0,5 (nach DIN EN 61298-2) | ||||||||||||
Repeatability [% of the span] | < ± 0,05; (with temperature fluctuations < 10 K) | ||||||||||||
Characteristics deviation [% of the span] | < ± 0,5; (linearity incl. hysteresis and repeatability, limit value setting to DIN EN IEC 62828-1) | ||||||||||||
Linearity deviation [% of the span] | < ± 0,1 (BFSL) / < ± 0,2 (LS) | ||||||||||||
Hysteresis deviation [% of the span] | < ± 0,2 | ||||||||||||
Long-term stability [% of the span] | < ± 0,1; (per 6 months) | ||||||||||||
Temperature coefficient zero point [% of the span / 10 K] | < 0,1 (-25...90 °C) / < 0,2 (-40...-25 °C) | ||||||||||||
Temperature coefficient span [% of the span / 10 K] | < 0,1 (-25...90 °C) / < 0,2 (-40...-25 °C) | ||||||||||||
Response times | |||||||||||||
Response time [ms] | < 3 | ||||||||||||
Software / programming | |||||||||||||
Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping | ||||||||||||
Interfaces | |||||||||||||
Communication interface | IO-Link | ||||||||||||
Transmission type | COM2 (38,4 kBaud) | ||||||||||||
IO-Link revision | 1.1 | ||||||||||||
SDCI standard | IEC 61131-9 | ||||||||||||
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis | ||||||||||||
SIO mode | yes | ||||||||||||
Required master port type | A | ||||||||||||
Process data analogue | 2 | ||||||||||||
Process data binary | 2 | ||||||||||||
Min. process cycle time [ms] | 5 | ||||||||||||
Supported DeviceIDs |
|
||||||||||||
Operating conditions | |||||||||||||
Ambient temperature [°C] | -40...90 | ||||||||||||
Storage temperature [°C] | -40...100 | ||||||||||||
Protection | IP 67; IP 69K | ||||||||||||
Tests / approvals | |||||||||||||
EMC |
|
||||||||||||
Shock resistance |
|
||||||||||||
Vibration resistance |
|
||||||||||||
MTTF [years] | 668 | ||||||||||||
UL approval |
|
||||||||||||
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request | ||||||||||||
Mechanical data | |||||||||||||
Weight [g] | 66 | ||||||||||||
Materials | 1.4542 (17-4 PH / 630); stainless steel (1.4404 / 316L); PEI | ||||||||||||
Materials (wetted parts) | stainless steel (1.4305 / 303); 1.4542 (17-4 PH / 630) | ||||||||||||
Min. pressure cycles | 60 million; (at 1.2 times nominal pressure) | ||||||||||||
Tightening torque [Nm] | 50; (recommended tightening torque; depends on lubrication, seal and pressure rating) | ||||||||||||
Process connection | threaded connection 1/4" NPT external thread internal thread:M5 | ||||||||||||
Restrictor element integrated | yes | ||||||||||||
Remarks | |||||||||||||
Remarks |
|
||||||||||||
Pack quantity | 1 pcs. | ||||||||||||
Electrical connection | |||||||||||||
Connection | Connector: 1 x M12; coding: A |