Output signal |
switching signal; IO-Link; (configurable) |
Measuring range |
0...250 bar | 0...3625 psi | 0...25 MPa | |
Process connection |
flange internal thread:G 1/4; internal thread:M6 |
Special feature |
Gold-plated contacts |
Design |
with flange adapter |
Media |
liquids and gases |
Conditionally suitable for |
use in gases at pressures &rt; 25 bar only on request |
Medium temperature [°C] |
-25...80 |
Min. bursting pressure |
|
Pressure rating |
|
Type of pressure |
relative pressure |
Operating voltage [V] |
18...36 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] |
< 50 |
Min. insulation resistance [MΩ] |
100; (500 V DC) |
Protection class |
III |
Reverse polarity protection |
yes |
Overvoltage protection |
yes; (< 40 V) |
Power-on delay time [s] |
0.3 |
Integrated watchdog |
yes |
Number of inputs and outputs |
Number of digital outputs: 2 |
Total number of outputs |
2 |
Output signal |
switching signal; IO-Link; (configurable) |
Electrical design |
PNP/NPN |
Number of digital outputs |
2 |
Output function |
normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] |
2 |
Permanent current rating of switching output DC [mA] |
250 |
Switching frequency DC [Hz] |
< 170 |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Measuring range |
0...250 bar | 0...3625 psi | 0...25 MPa | |
Set point SP |
2...250 bar | 40...3620 psi | 0.2...25 MPa | |
Reset point rP |
1...249 bar | 20...3600 psi | 0.1...24.9 MPa | |
In steps of |
|
Factory setting |
| SP1 = 63 bar | rP1 = 58 bar | | SP2 = 188 bar | rP2 = 183 bar | |
Switch point accuracy [% of the span] |
< ± 0,5 |
Repeatability [% of the span] |
< ± 0,1; (with temperature fluctuations < 10 K) |
Characteristics deviation [% of the span] |
< ± 0,5; (linearity, incl. hysteresis and repeatability , limit value setting to DIN EN IEC 62828-1) |
Hysteresis deviation [% of the span] |
< ± 0,25 |
Long-term stability [% of the span] |
< ± 0,05; (per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] |
0,2; (0...80 °C) |
Temperature coefficient span [% of the span / 10 K] |
0,2; (0...80 °C) |
Delay time programmable dS, dr [s] |
0; 0,2...50 |
Parameter setting options |
hysteresis / window; normally open / normally closed; diagnostic function; switching logic; switch-on/switch-off delay; Damping; Display unit |
Communication interface |
IO-Link |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.1 |
SDCI standard |
IEC 61131-9 CDV |
Profiles |
no profile |
SIO mode |
yes |
Required master port type |
A |
Process data analogue |
1 |
Process data binary |
2 |
Min. process cycle time [ms] |
2.3 |
Supported DeviceIDs |
Type of operation | DeviceID | Default | 308 | |
Ambient temperature [°C] |
-20...80 |
Storage temperature [°C] |
-40...100 |
Protection |
IP 67 |
EMC |
EN 61000-4-2 ESD | 4 kV CD / 8 kV AD | EN 61000-4-3 HF radiated | 10 V/m | EN 61000-4-4 Burst | 2 kV | EN 61000-4-5 Surge | 0,5/1 kV | EN 61000-4-6 HF conducted | 10 V | |
Shock resistance |
DIN IEC 68-2-27 | 50 g (11 ms) | |
Vibration resistance |
DIN IEC 68-2-6 | 20 g (10...2000 Hz) | |
MTTF [years] |
220 |
Pressure Equipment Directive |
Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Weight [g] |
382.5 |
Materials |
stainless steel (1.4301 / 304); PC; PBT; PEI; FKM |
Materials (wetted parts) |
steel (1.4104 / 430F); ceramics; FKM |
Min. pressure cycles |
100 million |
Process connection |
flange internal thread:G 1/4; internal thread:M6 |
Restrictor element integrated |
no |
Display |
Display unit | 3 x LED, green | switching status | 2 x LED, yellow | function display | alphanumeric display, 4-digit | measured values | alphanumeric display, 4-digit | |
Pack quantity |
1 pcs. |