Output signal |
switching signal |
Measuring range |
-1...10 bar | -14.5...145 psi | -100...1000 kPa | -0.1...1 MPa | |
Process connection |
threaded connection G 1/4 internal thread |
Special feature |
Gold-plated contacts |
Media |
liquids and gases |
Medium temperature [°C] |
-25...80 |
Min. bursting pressure |
|
Pressure rating |
|
Type of pressure |
relative pressure |
Operating voltage [V] |
18...36 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA] |
< 50 |
Min. insulation resistance [MΩ] |
100; (500 V DC) |
Protection class |
III |
Reverse polarity protection |
yes |
Overvoltage protection |
yes; (< 40 V) |
Power-on delay time [s] |
0.3 |
Integrated watchdog |
yes |
Number of inputs and outputs |
Number of digital outputs: 2 |
Total number of outputs |
2 |
Output signal |
switching signal |
Electrical design |
PNP/NPN |
Number of digital outputs |
2 |
Output function |
normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] |
2 |
Permanent current rating of switching output DC [mA] |
250 |
Switching frequency DC [Hz] |
< 170 |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Measuring range |
-1...10 bar | -14.5...145 psi | -100...1000 kPa | -0.1...1 MPa | |
Set point SP |
-0.9...10 bar | -12...145 psi | -0.09...1 MPa | |
Reset point rP |
-0.95...9.95 bar | -13...144 psi | -0.095...0.995 MPa | |
In steps of |
|
Switch point accuracy [% of the span] |
< ± 0,5 |
Repeatability [% of the span] |
< ± 0,1; (with temperature fluctuations < 10 K) |
Characteristics deviation [% of the span] |
< ± 0,5; (linearity, incl. hysteresis and repeatability , limit value setting to DIN EN IEC 62828-1) |
Hysteresis deviation [% of the span] |
< ± 0,25 |
Long-term stability [% of the span] |
< ± 0,05; (per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] |
0,2; (-20...80 °C) |
Temperature coefficient span [% of the span / 10 K] |
0,2; (-20...80 °C) |
Delay time programmable dS, dr [s] |
0; 0,2...50 |
Parameter setting options |
hysteresis / window; normally open / normally closed; diagnostic function; switching logic; switch-on/switch-off delay; Damping; Display unit |
Ambient temperature [°C] |
-20...80 |
Storage temperature [°C] |
-40...100 |
Protection |
IP 65 |
EMC |
EN 61000-4-2 ESD | 4 kV CD / 8 kV AD | EN 61000-4-3 HF radiated | 10 V/m | EN 61000-4-4 Burst | 2 kV | EN 61000-4-5 Surge | 0,5/1 kV | EN 61000-4-6 HF conducted | 10 V | |
Shock resistance |
DIN IEC 68-2-27 | 50 g (11 ms) | |
Vibration resistance |
DIN IEC 68-2-6 | 20 g (10...2000 Hz) | |
MTTF [years] |
219 |
Pressure Equipment Directive |
Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Weight [g] |
259 |
Materials |
stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM; PTFE |
Materials (wetted parts) |
stainless steel (1.4305 / 303); ceramics; FKM |
Min. pressure cycles |
100 million |
Process connection |
threaded connection G 1/4 internal thread |
Restrictor element integrated |
no (can be retrofitted) |
Display |
Display unit | 3 x LED, green | switching status | 2 x LED, yellow | function display | alphanumeric display, 4-digit | measured values | alphanumeric display, 4-digit | |
Pack quantity |
1 pcs. |