TA1321 - Temperature transmitter
PRODUCENT CODE: TA1321
CATEGORY: Compact transmitters for the food and beverage industry
Producer: ifm electronic
1039.50 PLN
(net)
7-14 days
The product is available on request
At the moment, the product is not available in our warehouse.
After placing the order, we will notify you of the expected delivery date of the product.
At the moment, the product is not available in our warehouse.
After placing the order, we will notify you of the expected delivery date of the product.
Fast shipping
Free delivery
from 1000 PLN (net)
Free delivery
from 1000 PLN (net)
Do you have questions about the product?
Ask an experienced consultant:
Ask an experienced consultant:
Description
TA-083C1EM38- A-ZVG/US
- Very short response time < 0.25 / < 1s
- Free 3-point calibration certificate available online
- High measuring range: -50...200°C
IO-Link features
- Precise analogue output and user-friendly communication via IO-Link
Technical data
Product characteristics | |||||
Number of inputs and outputs | Number of analogue outputs: 1 | ||||
Measuring range [°C] | -50...200 | ||||
Communication interface | IO-Link | ||||
Process connection | G 3/8 internal thread | ||||
Installation length EL [mm] | 83 | ||||
Application | |||||
Measuring element | 1 x Pt 1000; (to DIN EN 60751, class A) | ||||
Media | liquids and gases | ||||
Electrical data | |||||
Operating voltage [V] | 18...32 DC; ("supply class 2" to cULus) | ||||
Current consumption [mA] | < 50 | ||||
Protection class | III | ||||
Reverse polarity protection | yes | ||||
Power-on delay time [s] | 2 | ||||
Inputs / outputs | |||||
Number of inputs and outputs | Number of analogue outputs: 1 | ||||
Outputs | |||||
Total number of outputs | 1 | ||||
Output signal | analogue signal; IO-Link; (configurable) | ||||
Number of analogue outputs | 1 | ||||
Analogue current output [mA] | 4...20 | ||||
Max. load [Ω] | 250; ((18...19 V); 19...32 V: 300 Ω) | ||||
Short-circuit protection | yes | ||||
Overload protection | yes | ||||
Measuring/setting range | |||||
Measuring range [°C] | -50...200 | ||||
Factory setting | -10...150 °C | ||||
Resolution of analogue output [K] | 0.04 | ||||
Accuracy / deviations | |||||
Precision analogue output [K] | ± 0,3 + (± 0,1 % MS) | ||||
Temperature coefficient [% of the span / 10 K] | 0,1; (in case of deviation from the reference condition 25 ± 5 °C) | ||||
Response times | |||||
Dynamic response T05 / T09 [s] | < 0,25 / < 1 | ||||
Interfaces | |||||
Communication interface | IO-Link | ||||
Transmission type | COM2 (38,4 kBaud) | ||||
IO-Link revision | 1.1 | ||||
Operating conditions | |||||
Ambient temperature [°C] | -25...80 | ||||
Note on ambient temperature |
|
||||
Storage temperature [°C] | -40...100 | ||||
Protection | IP 67; IP 68; IP 69K | ||||
Tests / approvals | |||||
EMC |
|
||||
Shock resistance |
|
||||
Vibration resistance |
|
||||
MTTF [years] | 334 | ||||
Note on approval |
|
||||
UL approval |
|
||||
Mechanical data | |||||
Weight [g] | 175 | ||||
Housing | suitable for thermowell mounting | ||||
Materials | stainless steel (1.4404 / 316L); stainless steel (1.4122); PEI; FKM | ||||
Tightening torque [Nm] | 10 | ||||
Process connection | G 3/8 internal thread | ||||
Probe diameter [mm] | 3 | ||||
Installation length EL [mm] | 83 | ||||
Remarks | |||||
Remarks |
|
||||
Pack quantity | 1 pcs. | ||||
Electrical connection | |||||
Connection | Connector: 1 x M12; coding: A |