Hydrocont (Ex)S50
W chwili obecnej produkt nie jest dostępny w naszym magazynie.
Po złożeniu zamówienia, powiadomimy o przewidywanym terminie realizacji danego produktu.
Darmowa dostawa
od 1000 PLN (netto)
Zapytaj doświadczonego konsultanta:
Hydrostatic filling level measurement, suitable also for Ex areas
With dry capacitive measurement system and with display, 4-20mA or 0-10V output and 2 pnp switching outputs
- Hygene applications
- Precise ceramic cell
- Bright LED ensures exclent reading
The devices of the series Hydrocont® S50 with integrated digital evaluation electronic are compact sensors for measuring and monitoring of fill levels.
The excellent characteristics like highest strength against pressure and pressure blows, high resistance against chemicals and corrosion, very good insensitiveness against temperature shocks and EM interference, highest accuracy and long term stability and also low influence of temperature makes it possible to use the sensor in all pressureless containers for liquid medium like water, waste water, solvents, oil, sludge, grease, cleaning agents, etc.
The level measurement system Hydrocont® S50 is built in the wall of the medium container. The medium contacts directly the ceramic membrane of the sensor without using a pressure mediator liquid and causes there a deflection of the membrane because of the hydrostatic pressure of the medium.
At the maximum deflection the membrane contacts a robust ceramic carrier and because of this, the membrane come through over pressure of e.g. 80-times of nominal load at a sensor with a pressure range of 0…50 mbar without damage. The fill level proportional pressure signal of the ceramic membrane is recorded from a processor with high resolution, adjusted according to the settings and converted into a high resolution output signal of 4…20mA or 0…10V. By using 3 keys and an LED display the sensor measurement range, the display, the PNP-switching outputs and the damping can be adjusted or the behaviour in the case of failure and the release of the fast adjustment can be set.
Function
The level measurement system Hydrocont® S50 is built in the wall of the medium container.
The medium contacts directly the ceramic membrane of the sensor without using a pressure mediator liquid and causes there a deflection of the membrane because of the hydrostatic pressure of the medium.
At the maximum deflection the membrane contacts a robust ceramic carrier and because of this, the membrane come through over pressure of e.g. 80-times of nominal load at a sensor with a pressure range of 0…50 mbar without damage.
The fill level proportional pressure signal of the ceramic membrane is recorded from a processor with high resolution, adjusted according to the settings and converted into a high resolution output signal of 4…20mA or 0…10V.By using 3 keys and an LED display the sensor measurement range, the display, the PNP-switching outputs and the damping can be adjusted or the behaviour in the case of failure and the release of the fast adjustment can be set.
The switching state of the two PNP-switching output is signalled by one LED for every output.
Hilfsenergie | |
Ausgang Varianten A/B/C/D | 4 bis 20 mA, 2-Draht, Profibus PA |
Ausgang Varianten E/F/G/H | 0 bis 10 V, 3-Draht |
Zulässige Speisespannung | |
Variante C/D | 10,5 V bis 45 V DC |
Variante A/B/E/F/G/H | 14,5 V bis 45 V DC |
Restwelligkeit | ≤ 2 Vss |
Schaltausgänge (S1 / S2) | 2x PNP-schaltend auf +VS |
Ausgangsstrom | > 250 mA, strombegrenzt, kurzschlussfest |
Verzögerungszeit Ausgang | bei Dämpfung 1 T90 typ. 260 ms, max. 310 ms |
Einstellbereich Dämpfung | 0,3 bis 30 Sekunden / 100 Stufen |
Messgenauigkeit | |
Temperaturabweichung | ≤ 0,1% / 10 K der Nennmessspanne |
Kennlinienabweichung | ≤ 0,1% / 0,2% der Nennmessspanne |
Kalibrier-Abweichung | ≤ 0,05% der Nennmessspanne |
Langzeitdrift | ≤ 0,1% / Jahr der Nennmessspanne |
Speisespannungseinfluss | ≤ 0,02% / 10 V der Nennmessspanne |
Auflösung | besser 1 µA bzw. 0,5 mV (16 Bit = 65536 Stufen) |
Werkstoffe | |
Membran | Keramik Standard AL2O3 96% Keramik Hochrein AL2O3 99,9% |
Prozessanschluss | Stahl 1.4404 / andere auf Anfrage |
Temperaturtrennstück | Stahl 1.4404 / andere auf Anfrage |
Dichtungen | Viton® / EPDM / Neopren® / Perfluorelastomer |
Anschlussgehäuse | Stahl 1.4301 / PUM – Delrin® / PBT |
Tragkabel | PE/FEP |
Umgebungsbedingungen | |
Messstoffbedingungen | -40°C bis +125°C (für 1h 140°C); bei Tragkabel -20°C bis +70°C |
Umgebungs-/Lagertemperatur | -40°C bis +85°C; bei Tragkabel -20°C bis +70°C |
Schutzart | IP65/IP67 |