RSSG SS
Housing:
316 Stainless Steel, Resin Encapsulated
Contacts:
2NO + 1NC (with door open)
Contact Rating:
500mA 24VDC
Coding:
Uniquely Coded, RFID
Indication:
Bi-Colour LED (Open/Close Indication)
Ingress Protection Rating:
IP67 and IP69K
RSSG-SS are standalone, non-contact RFID safety switches. With 2NO + 1NC contacts, capable of switching 3A at 24Vdc & 230Vac. With tamper proof RFID switching, the RSSG-SS is suitable for use with safety relays with a low inrush current. A dual colour, built in LED helps the operator in speedy fault diagnosis. The RSSG-SS safety switches are available with 3, 6 or 10 metre pre-wired cables which are fully sealed and suitable for use in most wet / harsh environments
To view our animated video, please follow the link: RSSG-SS Video
Nazwa | Numer referencyjny | Cena |
---|---|---|
RSSG-SS-21-DC-03M | 364.028 | - |
RSSG-SS-21-DC-06M | 364.029 | - |
RSSG-SS-21-DC-10M | 364.030 | - |
RSSG-SS-ACT | 364.034 | - |
Specyfikacja techniczna | |
Opcje napięcia zasilania | 24VDC |
Pobór mocy | 2VA / 2W |
Wyjście bezpieczne | 2 X NO |
Ocena wyjścia bezpieczeństwa | 24Vdc/230Vac / 500mA |
Wyjście AUX | 1 X NC |
Ocena wyjścia AUX | 24Vdc/230Vac / 500mA |
Przewód/złącze | Okablowany |
Długość przewodu | 3, 6 lub 10 metrów |
Kodowanie | RFID, Uniquely coded |
Wskazanie | DUAL COLOUR LED |
Wymiary przełącznika (mm) | 88 X 25 X 20 |
Wymiary siłownika (mm) | 88 X 25 X 20 |
Klasa IP | IP67 / IP69K |
Budowa | 316 Stainless Steel |
Montaż | 4 x Śruby zabezpieczające M4 |
Parametry środowiskowe | |
Temperatura robocza | -25°C to +60°C |
Temperatura przechowywania | -10°C to +60°C |
Dane dotyczące bezpieczeństwa | |
PL zgodnie z EN ISO 13849-1 | E |
SIL CL zgodnie z EN IEC 62061 | 3 |
PFHd zgodnie z EN IEC 62061 | 4.3 x 10-8 |
PFH | 6.52 x 10-8 |
B10d | 2,000,000 |
MTTFd | > 100 lat (w oparciu o wskaźnik wykorzystania 360 dni) |
TM | > 20 lat |
DC | 99% |
SFF | 99% |
Notes | |
1) Based on dual channel wiring according to CAT 4. Diagnostic coverage provided by downstream control logic. DC - medium, MTTFd = 100 Years |