Position switches are used to monitor the position of moving parts of machines and plant. Can be used in safety circuits, as the device satisfies EN 60 947-5-1/DIN VDE 0660 part 200, and the opening contacts are positive opening. The position switch Series 8060 with positive opening contacts has been tested to the professional association test standard GS-ET 15 of the German Employer Liability Insurance Association, and is thus licensed for personnel protection functions. Category 1 Safety position switches have contact and actuating element in a single constructional and functional unit. Because of the galvanic isolation of the moving contacts, the position switch is suitable for switching various potentials.
The type 8060/1 position switch comprises a flameproof switching element fitted into an increased safety enclosure. A choice of actuators is available. It is used to switch auxiliary, control and signal circuits in hazardous areas.
Parametry 8060/1-1-S wyłącznik krańcowy R.Stahl / Technical Data for 8060/1-1 limit switch, R.Stahl
Explosion protection | |
Gas explosion protection | E II 2 G EEx ed IIC T6 |
Dust explosion protection | E II 2 D IP65 T80 °C |
Certificates | |
Gas explosion protection | PTB 01 ATEX 1052 |
Dust explosion protection | LCIE 03 ATEX 6307 |
Rated operational voltage Ue | | 8060/1-1 | 8060/1-3 |
| | 8060/1-2 | 8060/1-4 |
| | 8060/1-5 | |
| Alternating current for equal potential: | max. 500 V | max. 400 V |
| Alternating current for unequal potential: | max. 250 V | max. 250 V |
| Direct current: | 250 V | 250 V |
Rated working current Ie | max. 10 A |
Rated isolation voltage | 550 V |
Rated impulse withstand voltage | 6 kV |
Back-up fuse | 10 A gL / gG |
Contact block | |
Version | Slow-action contact |
Contact arrangement | 2-pole, galvanically isolated, with double break action |
Clearance between open contacts | less or equal 1,5 mm (Clearance distance ) 3 mm) |
Contacts | Silver-Nickel |
Life | |
mechanical | max. 10*6 Operations (ten to the sixth power) |
electrical | max. 10*6 Operations (ten to the sixth power) |
Enclosure contact block | Polyamide, glass fibre-reinforced |
Ambient temperature | - 20 °C ... + 70 °C (6 A) |
Degree of protection | IP 65 |
Enclosure | Polyamide, glass fibre-reinforced; black |
Cable glands | Cable entry 8161, M 20 x 1,5 |
Connection | With cable entry 8161: | For sheathed cable 4 x 2,5 mm2, Ø 6 - 13 mm; recommended 4 x 1,5 mm2 |
| With mounted cable: | Sheathed cable HK-SO-X05VV-F-OZ 4 x 1,5 mm2, cable length 6 m |
Terminals | 1 x 2,5 mm2 (solid) or 2 x 1 mm2 (flexible) |
Mechanical shock resistance | Snap-action contact: 2 g |
| Slow-action contact: 20 g |