Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Measuring range |
-50...400 mbar | -20...160.6 inH2O | -5...40 kPa |
|
Process connection |
threaded connection G 1 external thread sealing cone Attention: The unit must only be installed in a process connection for G1 sealing cone.; The G1A sealing cone of the unit is only suited for adapters with metal end stop. |
Special feature |
Gold-plated contacts |
Application |
flush mountable for the food and beverage industry |
Media |
viscous media and liquids with suspended particles; liquids and gases |
Medium temperature [°C] |
-25...150 |
Min. bursting pressure |
30000 mbar | 12044 inH2O | 3000 kPa |
|
Pressure rating |
8000 mbar | 3200 inH2O | 800 kPa |
|
Vacuum resistance [mbar] |
-1000 |
Type of pressure |
relative pressure; vacuum |
No dead space |
yes |
MAWP (for applications according to CRN) [bar] |
8 |
Min. insulation resistance [MΩ] |
100; (500 V DC) |
Protection class |
III |
Reverse polarity protection |
yes |
Integrated watchdog |
yes |
Operating voltage [V] |
20...30 DC |
Current consumption [mA] |
3.5...21.5 |
Power-on delay time [s] |
< 1 |
Operating voltage [V] |
18...30 DC |
Current consumption [mA] |
5...45; (430 bei max. Laststrom) |
Power-on delay time [s] |
< 0.5 |
Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Total number of outputs |
2 |
Output signal |
switching signal; analogue signal; IO-Link |
Electrical design |
PNP/NPN |
Number of digital outputs |
2 |
Output function |
normally open / normally closed; (parameterisable) |
Number of analogue outputs |
1 |
Analogue current output [mA] |
4...20, invertible; (scalable) |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Overload protection |
yes |
Max. load [Ω] |
300 |
Max. voltage drop switching output DC [V] |
2 |
Permanent current rating of switching output DC [mA] |
100 |
Switching frequency DC [Hz] |
125 |
Max. load [Ω] |
(Ub - 10 V) / 21,5 mA; 650 Ω (Ub = 24 V) |
Measuring range |
-50...400 mbar | -20...160.6 inH2O | -5...40 kPa |
|
Set point SP |
-49.4...400 mbar | -19.8...160.6 inH2O | -4.94...40 kPa |
|
Reset point rP |
-50...399.4 mbar | -20.1...160.3 inH2O | -5...39.94 kPa |
|
Analogue start point |
-50...320 mbar | -20.1...128.5 inH2O | -5...32 kPa |
|
Analogue end point |
30...400 mbar | 12...160.6 inH2O | 3...40 kPa |
|
Min. difference between SP and rP |
0.6 mbar | 0.3 inH2O | 0.06 kPa |
|
In steps of |
0.1 mbar | 0.1 inH2O | 0.01 kPa |
|
Factory setting |
| SP1 =100 mbar | rP1 = 92 mbar | | SP2 = 300 mbar | rP2 = 292 mbar | | ASP = 0.00 mbar | AEP = 400 mbar | | dAP = 2.00 s | dAA =2.00 s |
|
Measuring range |
-25...150 °C | -13...302 °F |
|
Switch point accuracy [% of the span] |
< ± 0,2; (DIN EN IEC 62828-1; Turn down 1:1) |
Repeatability [% of the span] |
< ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
Characteristics deviation [% of the span] |
< ± 0,2; (DIN IEC EN 62828-1 incl. zero point and span error, non-linearity, hysteresis; Turn down 1:1) |
Linearity deviation [% of the span] |
< ± 0,15; (Turn down 1:1) |
Hysteresis deviation [% of the span] |
< ± 0,15; (Turn down 1:1) |
Long-term stability [% of the span] |
< ± 0,1; (Turn down 1:1; per year) |
Total deviation over temperature range |
Temperature range | total deviation |
---|
-25...15 °C | Characteristics deviation ± 0,1 % of the span / 10 K | 15...80 °C | Characteristics deviation | 80...150 °C | Characteristics deviation ± 0,15 % of the span / 10 K |
|
Notes on the accuracy / deviation |
for further details see section Diagrams and graphs |
Accuracy [K] |
± 2,5+ (0,08 x ( Umgebungstemperatur - Mediumtemperatur )) |
Repeatability [K] |
± 0,2 |
Resolution [K] |
0.2 |
Damping process value dAP [s] |
0...99.99 |
Damping for the analogue output dAA [s] |
0...99.99 |
Step response time analogue output [ms] |
30 |
Min. response time of switching output (dAP) [ms] |
3 |
Step response time analogue output [ms] |
7 |
Dynamic response T05 / T09 [s] |
< 35 / < 135; (DIN EN 60751 water ; &rt; 0,9 m/s) |
Communication interface |
IO-Link |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.1 |
SDCI standard |
IEC 61131-9 |
Profiles |
Identification and Diagnosis (0x4000), Measurement Data Channel (0x800A) |
SIO mode |
yes |
Required master port type |
A |
Min. process cycle time [ms] |
5.6 |
IO-Link resolution pressure [mbar] |
0.02 |
IO-Link resolution temperature [K] |
0.2 |
IO-Link process data (cyclical) |
function | bit length |
---|
pressure | 32 | temperature | 32 | device status | 4 | binary switching information | 2 |
|
IO-Link functions (acyclical) |
application specific tag; internal temperature; operating hours counter; switching cycles counter; Pressure peak counter |
Supported DeviceIDs |
Type of operation | DeviceID |
---|
default | 1189 |
|
Ambient temperature [°C] |
-25...80 |
Storage temperature [°C] |
-40...100 |
Protection |
IP 67; IP 68; IP 69K |
EMC |
|
Shock resistance |
DIN EN 60068-2-27 | 50 g (11 ms) |
|
Vibration resistance |
DIN EN 60068-2-6 | 20 g (10...2000 Hz) |
|
MTTF [years] |
214 |
Note on approval |
factory certificate available as download at www.factory-certificate.ifm |
|
UL approval |
UL Approval no. | J049 | File number UL | E174189 |
|
Weight [g] |
395 |
Materials |
stainless steel (1.4404 / 316L); FKM; PTFE; PBT; PEI; PFA |
Materials (wetted parts) |
ceramics (99.9 % Al2O3); stainless steel (1.4435 / 316L); surface characteristics: Ra < 0,4 / Rz 4; PTFE |
Min. pressure cycles |
100 million |
Tightening torque [Nm] |
20 |
Process connection |
threaded connection G 1 external thread sealing cone Attention: The unit must only be installed in a process connection for G1 sealing cone.; The G1A sealing cone of the unit is only suited for adapters with metal end stop. |
Display |
Display unit | LED, green | switching status | LED, yellow | function display | alphanumeric display, 4-digit | measured values | alphanumeric display, 4-digit |
|
Display unit |
mbar; kPa; inH2O; mmWS |
Pack quantity |
1 pcs. |
Connection |
Connector: 1 x M12; coding: A; Contacts: gold-plated |
ambient temperature influence on the accuracy |
X | temperature |
---|
Y | total deviation |
---|
|